Smart Electric Meter
Smart Water Meter
Energy Consumption Solution
Others
Coming Soon
Single Phase Smart Energy Meter with GPRS
The DDZY150 is a cost-effective solution for smart metering, data reading and load balance operations. The meter goes with direct connection type, The meter is manufactured by ISO9001 standards and IP54 protection rating. It offers two way communication via modular Ethernet/GPRS/PLC/RF com port and allows dynamic AMI interactions and reliable metrological operations at the same time.
Main Features:
1. Automatic data logging usage and load profiles
2. Detection of significant reverse energy (SRE)
3. IEC62056-21 compliant optical & RS485 port allowing for easy data interrogation
4. On-demand and automatic load limiting profile settings
5. Built-in contactor and relay to remotely disconnect load and sub-meters (on request)
6. Tamper detection and event record such as cover open, black-out, magnetic field
7. Maximum demand measurement
8. Detailed power information such as phase voltage, current, total active power, reactive power, apparent power, total power factor, power grid frequency
9. PLC/ RF/ GPRS/GSM communication with a head-end AMR/AMI server
10. Time of Use (TOU) / 4 tariffs /8 time divisions /100 holidays
11. DLMS/COSEM , IEC62056 protocol compliant
Electrical parameters:
Nominal voltage Un |
240V |
|
|
Extended operating voltage range |
80%~115%Un |
|
|
Limited voltage |
60%~120%Un |
Nominal frequency fn |
50/60Hz+5% |
Current |
|
|
|
Direct connection type |
10(80)A,starting from 20mA |
Meter Constant |
|
|
|
Direct connection type |
1600imp/kWh |
Accuracy |
|
|
|
Active energy to IEC62053‐21 |
Class1.0 |
Power Consumption |
|
|
|
Power consumption in Voltage circuit |
<2W <8VA |
|
|
Power consumption in current circuit |
<1VA |
Temperature range |
|
|
|
Operation |
25℃ to+70℃ |
|
|
Storage |
40℃ to+85℃ |
Insulation strength |
|
AC Insulation strength |
4kV at 50Hz during 1min |
|
|
Impulse voltage 1.2/50μs mains connections |
8kV |
Electro Magnetic Compatibility |
|
Electrostatic discharges |
|
|
|
Contact discharge |
8kV |
|
|
Air discharge |
16kV |
RF immunity |
|
|
|
80MHz to 2GHz with load |
10V/m |
|
|
80MHz to 2GHz no load |
30V/m |
Fast transient burst test |
4kV |
|
|
Mechanical requirements |
|
Protection Rating |
IP54 |
|
|
Maximum cable size |
10 mm |
|
|
Insulation System Classification |
Protective Class II |